| Technical Parameter | Value |
| Rated Value |
AC voltage:AC/DC220V, AC/DC110V or DC48V
AC current: AC1A, 5A;
|
| Overload capacity |
1.2In, continuous working
20 times for 1 second
|
| power supply |
Rated: AC/DC220, AC/DC110V or DC48V
Permissible deviation: -20%-+20%
Power consumption: ≤15W
|
| Power Consumption | ≤0.5VA (single phase) |
| Measuring rage | 0-1.2In |
| Digital output |
Mechanical service life: ≥10000
Output mode: Passive contacts
Switching capacity: ≤4000W or ≤384VA
On-state current: ≥16A(AC250V/DC24V) in the continuous mode;
≥30A for a short term (200ms)
|
|
Accuracy
|
Class 0.5 |
|
RMS Voltage: ±0.1%
RMS Current: ±0.1%
P, Q, S: ±0.2%
Power factor: Class 0.5
Voltage deviation: 0.1%
Frequency deviation: ±0.001Hz
|
|
| Communication | RS485, Modbus-RTU protocol; Ethernet. |
| Three phase unbalance |
Voltage unbalance: ±0.15%
Current unbalance: ±1%
|
| Power frequency withstand voltage |
Between power supply set of terminals and signal input, output set of terminals 2kV/1min (RMS)
Between the shell and all set of terminals (except the set of terminals reference voltage less than 40V) AC 4kV
|
| Temperature | Operation: -10ºC~+55ºC; Storage: -30ºC-+80ºC |
| Humidity | ≤95%RH, no condensation, without corrosive gas |
| Altitude | ≤ 2500m |