Jiangsu Acrel Electrical Manufacturing Co., LTD.

APView power analyzer

Power quality monitor APView500 integrates a high-performance multi-core platform and an embedded operating system, and monitors power quality indexes stipulated in IEC61000-4-30 Testing and measurement techniques –Power quality measurement methods, and provides various functions such as harmonic analysis, waveform sampling, voltage dips/swells/interruptions monitoring, flicker monitoring , voltage unbalance monitoring, event recording and measurement control. It meets IEC 61000-4-30 Class A Edition 3.1 with respect to standardization of power quality index measurement methods, measurement accuracy of index parameters, clock synchronization, event alarms and others and satisfy the demands of power quality monitoring of power supply system up to 110kV. Therefore, it is widely applicable for power quality monitoring in chemical industry, steel industry, metallurgy industry, hospitals, data centers, transportation, construction industry and other industries.

General

  Power quality monitor APView500 integrates a high-performance multi-core platform and an embedded operating system, and monitors power quality indexes stipulated in IEC61000-4-30 Testing and measurement techniques –Power quality measurement methods, and provides various functions such as harmonic analysis, waveform sampling, voltage dips/swells/interruptions monitoring, flicker monitoring , voltage unbalance monitoring, event recording and measurement control. It meets IEC 61000-4-30 Class A Edition 3.1 with respect to standardization of power quality index measurement methods, measurement accuracy of index parameters, clock synchronization, event alarms and others and satisfy the demands of power quality monitoring of power supply system up to 110kV. Therefore, it is widely applicable for power quality monitoring in chemical industry, steel industry, metallurgy industry, hospitals, data centers, transportation, construction industry and other industries.

Parameters

Communication

RS485

(Modbus-RTU

Modbus-TCP、IEC61850 MMS、FTP)

Rated: AC current 5A or 1A

       AC voltage

Rated: 57.74V/100V, or 220V/380V

Measuring range: 0-1.2Un

Power consumption:≤0.5VA (single phase)

Overload capacity: 1.2Un, continuous working

4 times for 1seconds

Technical Datasheet

Technical Parameter Value
Rated Value AC voltage:AC/DC220V, AC/DC110V or DC48V

AC current:AC1A,5A;

Overload capacity 1.2In, continuous working

20 times for 1 second

power supply Rated: AC/DC220, AC/DC110V or DC48V

Permissible deviation: -20%-+20%

Power consumption:≤15W

Power Consumption ≤0.5VA (single phase)
Measuring rage 0-1.2In
Digital output Mechanical service life: ≥10000

Output mode: Passive contacts

Switching capacity: ≤4000W or ≤384VA

On-state current: ≥16A(AC250V/DC24V) in the continuous mode;

≥30A for a short term (200ms)

Accuracy Class 0.5
RMS Voltage:±0.1%

RMS Current:±0.1%

P,Q,S:±0.2%

Power factor:Class 0.5

Voltage deviation:0.1%

Frequency deviation:±0.001Hz

Communication RS485,Modbus-RTU protocol;Ethernet.
Three phase unbalance Voltage unbalance:±0.15%

Current unbalance:±1%

Power frequency withstand voltage Between power supply set of terminals and signal input,output set of terminals 2kV/1min (RMS)

Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV

Temperature Operation: -10℃~+55℃Storage: -30℃-+80℃
Humidity ≤95%RH,no condensation,without corrosive gas
Altitude ≤ 2500m

Dimension

Installation

Wiring

Network

Related Products

Inquiry Now

Would you like to get information about Acrel? We appreciate your interest and would be happy to advise you.Simply give us some information so we can get in touch with you

Contact us

We will contact you within 24 hours.

弹窗表单