Jiangsu Acrel Electrical Manufacturing Co., LTD.

APM520 Power Quality Monitoring Meter

● Full Power Measurement

● Power Quality Analysis

● Leakage Current Measurement (Optional)

● Support Modbus-RTU/TCP Protocol

● Accuracy: 0.5s

General

APM5 series network power meter (hereinafter referred to as the meter) is designed according to IEC international standards, with full power measurement, power statistics, power quality analysis (including harmonics, interharmonics, flicker), fault recording function (including voltage temporary rise and fall interrupt, inrush current and other records), event recording function and network communication and other functions. It is mainly used for comprehensive monitoring of power supply quality in the power grid.

Parameter

Accuracy

 

Voltage、current and power: Class 0.2

Active power: Class 0.5; Reactive power: Class 1

 

Pulse Output

Output mode: photocoupler pulse with open collector;

Pulse constant: 10000imp/kWh (default)

Consumption

Voltage、current: Power consumption: <0.5VA;

Auxiliary power supply: Power consumption ≤15VA

Starting Current: 0.1%

Installation: Panel mounted

Frequency: Range: 45-65Hz

Relay: 3A/AC250V, 3A/DC30V

Dimension (L*W*H)

Panel size (L×W): 75*75mm

Cut-out size (L×W): 67*67mm

Auxiliary Power Supply

AC/DC 85V~265V or AC/DC 115~415V

Display

Front Panel

① Type of Parameters

② Load Value

③ Total Power

④ DO Status Indicator

⑤ Menu

⑥ Key Down

⑦ Data Display

⑧ Navbar

⑨ DI Status Indicator

⑩ Enter Button

⑪ Key up

Wiring

Network

Installation

① Cut out a 67*67mm hole on the panel. (If not existed)

② Unleash all the static, move off installation  terminal, put in the panel.

③ Fixed the meter on panel by using the incidental brackets with buckle.

④ Installation complete.

Application

Mining

Petrochemical

Building

Hotel

Municipal Project

Transportation

Hospital

Electric Safety

FAQ

Q: What’s the storage capacity, storage format and data storage interval of SD card?

A: The meter is equiped with standard 4G SD card while saving the data of electrical parameter, energy, event, SOE, alarm. Also, the setting of storage interval could be changed. (1 min interval for electrical parameter and 1 hour interval for energy)

Q: How should I select the expanded modules of APM5xx?

A: Our users can select 3 of the optional modules at will even repeatly except for communication module. Also, the order of module installation could be random

Q: The features of APM5xx?

A: Except for wave record and flicker record function, 0.2S measuring accuracy can also be a option. Also, users can measure the data through browser by using Ethernet auto WEB.

Q: As for the auxiliary power supply of APM5xx?

A: AC/DC 85~265V or 115~415V is both optional. Also, 380V  line voltage can also serve as power supply.

Package

MINIMUM PACKAGE
MINIMUM PACKAGE Package Dimension(1 PC)

170*150*130mm

Package Weight(1 PC)

0.78Kg

WHOLE BOX PACKAGE Package Dimension(36 PCS)

540*530*480mm

Package Weight(36 PCS)

15.2kG

PRODUCT HS CODE 9028301400

 

ATTENTION !
The above packing and weight data are only refer to model APM510.
For other models or optional functions, please contact the salesman for details, thank you for your cooperation!