| Technical Parameter | Indicators | |||
| Input | Frequency | 45~65Hz; | ||
| Voltage | Rated value: AC 3×220V/380V; | |||
| Overload: 1.2 times the rated value (continuous); 2 times the rated value/1 second; | ||||
| Power consumption: ≤ 0.5VA (per circuit); | ||||
| Current | Rated value: AC 100A; | |||
| Overload: 1.2 times the rated value (continuous); 10 times rated value/1 second; | ||||
| Power consumption: ≤ 0.5VA (per circuit); | ||||
| Function | Reserved pulse output | Output mode: optocoupler pulse with Open collector; | ||
| Communication | Modbus RTU protocol ; Baud 1200~38400 | |||
| Switch-ing | input | 4 dry contact inputs, 2 active (AC 220V input) | ||
| output | Output method: relay normally open contact output; Contact capacity: AC 250V/3A DC 30V/3A; | |||
| Temperature | Temperature: -20-100 ℃ (accuracy ± 2 ℃) | |||
| Measurement accuracy | Frequency 0.05Hz, voltage and current level 0.5, active energy level 1 | |||
| Auxiliary power supply | AC/DC 85 to 265V; power consumption ≤ 10VA; | |||
| Security
|
power-frequency withstand voltage | >AC 2kV/1min; | ||
| insulation resistance | Input and output terminals to casing>100M Ω; | |||
| Environment | Working temperature:-20℃~+60℃;
Storage temperature:-40℃~+70℃; Relative humidity:≤ 95% without condensation; Altitude: ≤ 2500m; |
|||
| Electromagnetic compatibility | Surge (impact) immunity test level 4; | |||
| Electrostatic discharge immunity test level 3 | ||||
| Electrical fast transient pulse group immunity test level 3 | ||||