AMC200L-12DE DC Multi-Channel Power Meter For Tower Base Station Power Monitor

  • Measurement: 3-phase U, I, P and etc
  • Frequency: Voltage,Current Class 0.5,Power Class 1.0
  • Rated Voltage: DC -48V
  • Rated Current: 12 Channels Hall Current Sensor:Hall sensor secondary side DC 5V access
  • Communication: RS485 (MODBUS-RTU), 4G
  • Function: 6DI/2DO, 2 NTC, 1T&H
  • Power supply: DC-40V~-60V

Parameter

Technical Parameter Technical Indicator
Input DC Voltage One channel:DC -48V
DC Current 12 Channels Hall Current Sensor:Hall sensor secondary side DC 5V access
State Grid Monitoring One channel:DC 0-5V
Overload Voltage: 1.2 times for 1 second, 2 times for 1 second; Current: 1.2 times for 1 second, 10 times for 1 second
Frequency Voltage,Current Class 0.5,Power Class 1.0
Resolution The voltage output accuracy is 0.01V, the current output accuracy is 0.01A, the power output accuracy is 0.01kW, and the power output accuracy is 0.01kWh
Function Basic Function Monitoring equipment system time, total voltage, total output current, total power, total electrical energy, voltage of each sub channel, current of each sub channel, power of each sub channel, electrical energy of each sub channel; RS485 communication
Alarm Function DC voltage output too low alarm, DC voltage output too high alarm, one-time power-off alarm, module voltage loss alarm, metering sub channel error alarm, internal program error alarm, clock error alarm, memory unit failure alarm, AC input power failure alarm
Timing function Support broadcast timing, remote timing calibration of metering module can be carried out through RS485 communication interface
Communication
Single-channel RS485, the default baud rate is 9600bps, and can be set to
1200-9600bps. Communication protocol: YD/T1363 protocol or Modbus RTU
protocol
Hall power supply A set of ±12V power output
Humidity And Temperature 4 Channels NTC Temperature Monitoring:Temperature:-20-100℃(Accuracy±2℃)

Humidity:20-90%RH(Accuracy ±5%RH)

Auxiliary power Voltage Range DC -40V~-60V
Power consumption The whole device≤2W (without Hall power supply output)
Storage It has the storage function of historical energy data and historical alarm information
Insulation resistance ≥40MΩ
Environment Temperature Working Temperature:-20℃~+60℃;Storage Temperature:-40℃~+70℃
Humidity ≤98% no condensation, no corrosive gas place
Altitude ≤4000m