Base station dedicated DC energy meter AMC16-DETT is specially designed for base stations where have sharing requirements, and switch power supply is without the function of sub-user metering.
The meter could measure6 circuits DC energy, and supply working current to the matched hall sensors. Meanwhile, it can realize zero drift calibration by upper computer software.have the functions of telemetering,teleindication,teleadjusting, metering at real time,energy quality abnormal alarm, data storage and processing, data interaction.
![]() |
Communication
Single channel RS485 communication protocol Standard or customized Rated U and I Total 200A/5V Accuracy 1%In≤I≤10%In error±2.5%;I>10%In error±2% Voltage range -40V~-60VDC Power consumption ≤2W( no hall power supply output) |
| Power supply output
+12V/100Ma, -12V/50mA Power consumption ≤2W( no hall power supply output) Dimension(L*W*H) 89.7*87.8*52mm Installation DIN 35 mm Clock ≤0.5S/d(23℃), ≤1S/d(-20℃-60℃) Current 1.2 times continued |
![]() |
| Technical parameter | Index | |
| Input | DC rated voltage | 1 channel: -48VDC |
| DC current | 6 channels hall sensors: total 200A/5V, China Telecom, China Mobile, China Unicom and the 1st channel reserve 50A/5V, 2nd channel reserve 100A/5V |
|
| Commercial power monitoring |
1 channel: 0-5VDC | |
| Overload capacity | Voltage:1.2times continued,2 times continued 1s; Current: 1.2 times continued,10 times continued 1s |
|
| Accuracy (superposition hall sensors) | 1%In≤I≤10%In error±2.5%; I>10%In error±2% | |
| Measurement resolution | Voltage output accuracy 0.01V; current output accuracy 0.01A; power output accuracy 0.01kw; energy output accuracy 0.01kwh |
|
| Functions | Basic function | Monitor device system time, total voltage, output total current, power, energy, each channel voltage, current, power, energy; LED indicator display;485 communication. |
| Metering function | Start current: under rated voltage, when the load current value of the meter doesn’t exceed 1% of the max. current, the meter starts. Shunt running current: when there is no current in the current circuit of the meter, and 85%-125%of the rated voltage is applied on the voltage circuit, the calculator shall not have more than one digital change. |
|
| Alarm function | DC voltage output low alarm,DC voltage output high alarm,one power down alarm, module voltage loss alarm, metering branch error alarm, internal program error alarm, clock error alarm, memory failure alarm, AC input power failure alarm |
|
| Timing function | support broadcast timing, could remote timing to the meter through RS485 communication. |
|
| Communication | Single channel RS485, baudrate 9600bps, can be set to 1200BPS, 2400bps, 4800bps. Communication protocol: standard or custmized |
|
| Hall sensor power supply | Power supply output:+12V/100Ma, -12V/50mA | |
| Clock accuracy | ≤0.5S/d(23℃), ≤1S/d(-20℃-60℃), | |
| Auxiliary supply |
Voltage range | -40V~-60VDC |
| Power consumption | Whole device≤2W( no hall power supply output) | |
| Storage | It has the storage function of historical power data and historical alarm information, and the memory is 2MB | |
| Insulation resistance | ≥40MΩ | |
| Environment | Temperature | Working : -20℃~+60℃; storage:-40℃~+70℃ |
| Humidity | ≤98% no condensation, no corrosive gas place | |
| Altitude | ≤4000m | |
| Protection level | IP20 | |
| Material flame retardent | Terminal glow wire temperature 960℃±10℃ ,shell glow wire temperature 6500℃±15℃ |
|
| Installation | Standard 35mm din rail | |
| Lightning protection |
Voltage input (differential mode) |
Peak value 5kA |
| Auxiliary supply (differential mode) |
Peak value 5kA | |
![]() |
① Digital input ② Brand/Model ③ Panel ④ Digital output ⑤ Pluse output |



Q:The measurement of the metering module is inaccurate.
A:Check input whether the polarity and direction of the input voltage and current wiring are correct;Whether the direction of the primary current of the Hall sensor is correct; Whether the output signal of the Hall sensor matches the input signal required by the module; Check whether the output negative pole of the voltage output Hall sensor is connected to the module GND.
Q:Communication is abnormal.
A:Check communication whether the communication cable is normal; check whether the communication terminals A and B are staggered; check whether the address of the module is set correctly and whether the communication baud rate is set correctly; if the communication of multiple modules is not normal, first try whether the single-machine communication is normal.
Q:The metering module cannot bedisplayed normally.
A:Check whether it is caused by insufficient load capacity due to the built-in power supply to the hall sensor. Change the external switching power supply to power the hall.
| MINIMUM PACKAGE | ![]() |
![]() |
![]() |
![]() |
| MINIMUM PAKAGE | Package dimensions(1 PC)
170*150*130mm |
Pakage Weight(1 PC)
0.31Kg |
||
| WHOLE BOX PAKAGE | Package dimensions(36 PCS)
535*525*475mm |
Pakage Weight(36 PCS)
11.16kG |
||
| PRODUCT HS CODE | 9028309000 | |||
ATTENTION !
The above packing and weight data are only refer to model AMC16-DETT.
For other models or optional functions, please contact the salesman for details, thank you for your cooperation!