| Item | Parameter | |
| Supply voltage | Supply voltage Us | AC/DC 85~265V |
| Frequency | 50/60Hz | |
| Power consumption | ≤ 5 W | |
| IT system being monitored | Nominal system voltage with ACPD300, Un | DC 50…1000V |
| Nominal system voltage without ACPD300, Un | DC 50…400V | |
| Response values | Response value (Insulation prewarning) | Insulation alarm limit value…2MΩ |
| Response value (Insulation alarm) | 1kΩ…2MΩ | |
| Relative uncertainty | ±15%,±2kΩ | |
| Undervoltage detection | (80%~100%) Un(off)* | |
| Overvoltage detection | (100%~120%) Un(off)* | |
| accuracy | 1%,±1V | |
| CCS and CHAdeMO 3.0 mode | Permissible system leakage capacitance | ≤20μF |
| Measuring and display range of insulation resistance | 1kΩ…2MΩ | |
| Measurement uncertainty / Relative uncertainty | Ce≤5μF: ±15%,±2 kΩ | |
| Ce>5μF and RF>100 kΩ: ±15% | ||
| Response time | ≤10s | |
| Interface | RS485/Modbus-RTU | |
| Relay output | 2 x 1 n/o contact, AC 250V,3A, DC 30V,5A | |
| Environment | Operating temperature | -10℃ ~ +55℃ |
| Storage temperature | -20℃ ~ +70℃ | |
| Humidity | ≤95%RH, no condensation and corrosive gas | |
| Altitude | ≤2000m | |
| weight | AIM-D500-CA | 244.3g |
| ACPD300 | 86.1g | |
| Certification | CE, IEC,RoHS | |



Would you like to get information about Acrel? We appreciate your interest and would be happy to advise you.Simply give us some information so we can get in touch with you